Carrier Frequency
C6-03
C6-04
* K is the coefficient determined by the set value in C6-03.
To fix the carrier frequency, set C6-03 and C6-04 to the same value, or set C6-05 to 0.
An OPE11 (Data setting error) will occur, i
C6-03 < C6-04.
Carrier Frequency and Current Derating
The default carrier frequency for the Normal Duty 1 mode depends on the inverter capacity. The overload
capability is 120% of the Normal Duty 1 rated current for 1 minute.
If the carrier frequency is set to a higher value than the factory setting, the overload capability is reduced like
shown in
Fig
6.2.
120%
96%
90%
0
Fig 6.2 Overload Capability depending on Carrier Frequency
Output frequency x C6-05 x K*
C6-03 ≥ 10.0 kHz: K=3
10.0 kHz > C6-03 ≥ 5.0 kHz: K=2
5.0 kHz > C6-03: K=1
Fig 6.1 Carrier Frequency Gain Settings
f the carrier frequency proportional gain (C6-05) > 6 and
200V Class 37 to 90kW
400V Class 75 to 110kW
400V Class 132kW
400V Class 160kW
5kHz
8kHz
10kHz
Output frequency
E1-04
Max. Output Frequency
200V Class 0.4 to 22kW
400V Class 0.4 to 22kW
200V Class 30kW
400V Class 30 to 55kW
Carrier Freq.
15kHz
6
3
6-