Setting
Value
1E
Analog frequency reference sample/hold
External fault
20 to 2F
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
30
PI control integral reset (reset when reset command is input or when stopped during PI control)
31
PI control integral hold (ON: Hold)
34
PI soft starter disable (ON: disabled)
35
PI input characteristics switch
36
Operation Source Option/Inverter selection 2 (ON: inverter settings)
60
Motor pre-heat command (ON: Performs motor pre-heat)
61
External search command 1 (ON: Speed search from maximum output frequency)
62
External search command 2 (ON: Speed search from set frequency)
64
External speed search command 3
65
Kinetic energy buffering (deceleration at momentary power loss) command (NC contact)
66
Kinetic energy buffering (deceleration at momentary power loss) command (NO contact)
67
Communications test mode
68
High-slip braking (HSB)
69
Jog Frequency 2
6A
Drive enable (NC, ON: Drive enabled, OFF: Drive disabled)
6B
Operation Source Communication/Inverter selection (ON: RS-422/485 port)
6C
Operation Source Communication/Inverter selection 2 (ON: inverter settings)
6D*
AUTO mode selection (ON: AUTO mode active)
6E*
HAND mode selection (ON: HAND mode active)
70
Bypass Drive Enable
* This parameter is effective only, if the HOA operator JVOP-162 is used.
Multi-function Contact Outputs: H2
Param-
eter
Name
Number
Terminal M1-M2
Multi-function contact
H2-01
function selection
output 1
Terminal M3-M4
Multi-function contact
H2-02
function selection
output 2
Multi-function Contact Output Functions
Setting
Value
0
During run (ON: run command is ON or voltage is being output)
1
Zero-speed
f
/f
agree 1 (detection width L4-02 is used.)
2
ref
out
f
/f
agree 1 (ON: Output frequency = ±L4-01, with detection width L4-02 used and during
ref
set
3
frequency agree)
Frequency detection 1 (ON: +L4-01 ≥ output frequency ≥ -L4-01, with detection width L4-02
4
used)
Frequency detection 2 (ON: Output frequency ≥ +L4-01 or output frequency ≤ -L4-01, with
5
detection width L4-02 used)
Function
Setting
Description
Range
0 to 38
0 to 38
Function
Change
MEMO-
Factory
during
Access
BUS
Setting
Opera-
Level
Register
tion
0
No
A
40BH
1
No
A
40CH
Page
6-57
6-60
6-84
6-84
6-84
6-84
6-58
6-13
6-38
6-38
6-38
6-82
6-102
6-6
6-52
6-58
5
6-58
6-59
6-59
6-52
Page
Page
6-61
6-62
6-25
6-25
6-25
6-25
27
5-

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents