Display
External fault (Input terminal S3)
(blink-
ing)
External fault (Input terminal S4)
(blink-
ing)
External fault (Input terminal S5)
(blink-
ing)
External fault (Input terminal S6)
(blink-
ing)
External fault (Input terminal S7)
(blink-
ing)
PI Feedback Lost
A PI feedback loss detection is
enabled (b5-12 ≠ 0) and the PI feed-
back input was less than b5-13 (PI
(blink-
feedback loss detection level) for
ing)
longer than the time set in b5-14 (PI
feedback loss detection time).
MEMOBUS Communications Error
Normal receive was not possible for
(blink-
2 s or longer after received control
ing)
data.
Option Card Communications Error
A communications error occurred in
a mode where the run command or a
(blink-
frequency reference is set from an
ing)
Communications Option Card.
7
Communications on Standby
Control data was not normally
(blink-
received when power was turned
ing)
ON.
Drive not enabled
(blink-
ing)
Cannot Reset
(blink-
ing)
8
7-
Meaning
An external fault was input from a
multi-function input terminal (S3 to
S7).
An digital input is programmed to
6A (Drive Enable) or 70 (Bypass
Drive Enable) and a RUN command
was input while the drive was not
enabled.
It is tried to reset a fault while a RUN
command is still active.
Probable causes
Remove the cause of the external
fault.
Check the communications devices
and signals.
Check the communications devices
and signals.
Check the communications devices
and signals.
Check the wiring and sequence of
the external signals.
Remove the RUN command and
reset.
Corrective Actions