Omron VARISPEED E7 User Manual page 218

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Register No.
Inverter status
Bit 0
Bit 1
Bit 2
Bit 3
Bit 4
Bit 5
Bit 6
002CH
Bit 7
Bit 8
Bit 9
Bit A
Bit B
Bit C
Bit D
Bit E
Bit F
Multi-function contact output status
Bit 0
002DH
Bit 1
Bit 2
Bits 3 to F
002EH - 0030H
Not used
0031H
Main circuit DC voltage
0032H – 0037H
Not used
0038H
PI feedback (max. output frequency
0039H
PI input (max. output frequency
003AH
PI output (max. output frequency
003BH
CPU software number
003CH
Flash software number
Communications error details
Bit 0
Bit 1
Bit 2
003DH
Bit 3
Bit 4
Bit 5
Bit 6
Bits 7 to F
003EH
kVA setting
Note:Communications error details are stored until an error reset is input (you can also reset while the Unit is operating).
Contents
Operation
Zero speed
Frequency agree
User-defined speed agree
Frequency detection 1
Frequency detection 2
Inverter startup completed
Undervoltage detection
Baseblock
Frequency reference mode
Run command mode
Overtorque detection
Frequency reference lost
Restart enabled
Error (including MEMOBUS communications time-out) 1:Error occurred
MEMOBUS communications time-out 1: Timed out
Multi-function contact output 1 (terminal M1-M2) 1: ON 0: OFF
Multi-function contact output 2 (terminal M3-M4) 1: ON 0: OFF
Not used
Not used
^
=
100%; resolution 0.1%; without sign)
^
=
100%; resolution 0.1%; with sign)
^
=
100%; resolution 0.1%; with sign)
CRC error
Invalid data length
Not used
Parity error
Overrun error
Framing error
Time-out
Not used
1: Operating
1: Zero speed
1: Agreement
1: Agreement
1: Output frequency ≤ L4-01
1: Output frequency ≥ L4-01
1: Startup completed
1: Detected
1: Inverter output baseblock
1: Not communication 0: Communication option
1: Not communication 0: Communication option
1: Detected
1: Lost
1: Restarting