Setting Precautions
The stall prevention level during deceleration differs depending on the inverter rated voltage and input
•
voltage. Refer to the following table for details.
200 V class
400 V class
When using the braking option, be sure to set parameter L3-04 to 0.
•
6
20
6-
Inverter Rated/Input Voltage
E1-01 ≥ 400 V
E1-01 < 400 V
Stall Prevention Level during Deceleration (V)
380
760
660