Data Tables
The data tables are shown below. The types of data are as follows: Reference data, monitor data, and broadcast
data.
Reference Data
The reference data table is shown below. These data can be read and written. They cannot be used for monitor-
ing functions.
Register No.
0000H
0001H
0002H
0003H to 0005H
0006H
6
0007H
0008H
0009H
000AH to 000EH
000FH
Note:Write 0 to all unused bits. Also, do not write data to reserved registers.
74
6-
Reserved
Run operation and input commands
Bit 0
Run/stop command
Bit 1
Forward/reverse operation
Bit 2
External error
Bit 3
Error reset
Bit 4
ComNet
Bit 5
ComCtrl
Bit 6
Multi-function input command 3
Bit 7
Multi-function input command 4
Bit 8
Multi-function input command 5
Bit 9
Multi-function input command 6
Bit A
Multi-function input command 7
Bits B to F
Not used
Frequency reference (Set units using parameter o1-03)
Not used
PI target value
Analog output 1 setting (-11 V/-726 to 11 V/726) → 10V = 660
Analog output 2 setting (-11 V/-726 to 11 V/726) → 10V = 660
Multi-function contact output setting
Bit 0
Contact output 1 (Terminal M1-M2)
Bit 1
Contact output 2 (Terminal M3-M4)
Bit 2
Not used
Bits 3 to 5
Not used
Bit 6
Set error contact (terminal MA-MC) output using bit 7. 1: ON 0: OFF
Bit 7
Error contact (terminal MA-MC)
Bits 8 to F
Not used
Not used
Reference selection settings
Bit 0
Not used
Bit 1
Input PI target value
Bits 3 to B
Not used
C
Broadcast data terminal S5 input
D
Broadcast data terminal S6 input
E
Broadcast data terminal S7 input
F
Not used
Contents
1: Run 0: Stop
1: Reverse 0: Forward
1: Error (EFO)
1: Reset command
1: ON 0: OFF
1: ON 0: OFF
1: ON 0: OFF
1: Enabled 0: Disabled
1: Enabled 0: Disabled
1: Enabled 0: Disabled
1: Enabled 0: Disabled