MEMOBUS Message Example
An example of MEMOBUS command/response messages is given below.
Reading Inverter Memory Register Contents
The content of maximum 16 inverter memory registers can be readout at a time.
Among other things the command message must contain the start address of the first register that is to be read
out and the quantity of registers that should be read out. The response message will contain the content of the
first and the consecutive number of registers that has been set for the quantity.
The contents of the memory register are separated into higher 8 bits and lower 8 bits.
The following tables show message examples when reading status signals, error details, data link status, and
frequency references from the slave 2 Inverter.
Slave Address
Function Code
Start
Address
Quantity
CRC-16
6
72
6-
Command Message
02H
03H
Higher
00H
Lower
20H
Higher
00H
Lower
04H
Higher
45H
Lower
F0H
Response Message
(During Normal Operation)
Slave Address
02H
Function Code
03H
Data quantity
08H
Higher
00H
1st storage
register
Lower
65H
Higher
00H
Next stor-
age register
Lower
00H
Higher
00H
Next stor-
age register
Lower
00H
Higher
01H
Next stor-
age register
Lower
F4H
Higher
AFH
CRC-16
Lower
82H
Response Message
(During Error)
Slave Address
02H
Function Code
83H
Error code
03H
Higher
F1H
CRC-16
Lower
31H