Omron VARISPEED E7 User Manual page 127

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Multi-function Selections: o2
Param-
eter
Number
LOCAL/
o2-01
REMOTE key
enable/disable
STOP key during
control circuit
o2-02
terminal opera-
tion
User parameter
o2-03
initial value
5
o2-04 kVA selection
Frequency refer-
o2-05
ence setting
method selection
Operation selec-
tion when digital
o2-06
operator is dis-
connected
Cumulative oper-
o2-07
ation time setting
Cumulative oper-
o2-08
ation time selec-
tion
40
5-
Name
Description
Sets the Digital Operator Local/
Remote key
0: Disabled
1: Enabled (Switches between the
Digital Operator and the param-
eter settings b1-01, b1-02.)
Sets the Stop key in the run mode.
0: Disabled (When the run com-
mand is issued from an external
terminal, the Stop key is disa-
bled.)
1: Enabled (Effective even during
run.)
Clears or stores user initial values.
0: Stores/not set
1: Begins storing (Records the set
parameters as user initial val-
ues.)
2: All clear (Clears all recorded
user initial values)
When the set parameters are
recorded as user initial values,
1110 will be set in A1-03.
Do not set unless using a control
board from an Inverter with a dif-
ferent capacity.
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter key is necessary
or not.
0: Enter key needed
1: Enter key not needed
When set to 1, the Inverter accepts
the frequency reference without
Enter key operation.
Sets the operation when the Digital
Operator is disconnected.
0: Disabled (Operation continues
even if the Digital Operator is
disconnected.)
1: Enabled (OPR is detected at
Digital Operator disconnection.
Inverter output is switched off,
and fault contact is operated.)
Sets the cumulative operation time
in hour units.
Operation time is calculated from
the set values.
0: Cumulative time when the
Inverter power is on. (All time
while the Inverter power is on is
accumulated.)
1: Cumulative Inverter run time.
(Only Inverter output time is
accumulated.)
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 or 1
1
No
A
0 or 1
1
No
A
0 to 2
0
No
A
0 to FF
0
No
A
0 or 1
0
No
A
0 or 1
0
No
A
0 to
0 hr.
No
A
65535
0 or 1
0
No
A
MEMO-
BUS
Page
Register
505H
6-105
506H
6-105
507H
6-105
508H
5-49
509H
6-105
50AH
6-105
50BH
6-105
50CH
6-105