Torque Detection: L6
Param-
eter
Number
Torque detection
L6-01
selection
5
Torque detection
L6-02
level
Torque detection
L6-03
time
36
5-
Name
Description
0: Overtorque/undertorque detec-
tion disabled.
1: Overtorque detection only with
speed agreement; operation
continues (warning is output).
2: Overtorque detected continu-
ously during operation; opera-
tion continues (warning is
output).
3: Overtorque detection only with
speed agreement; output
stopped upon detection.
4: Overtorque detected continu-
ously during operation; output
stopped upon detection.
5: Undertorque detection only
with speed agreement; opera-
tion continues (warning is out-
put).
6: Undertorque detected continu-
ously during operation; opera-
tion continues (warning is
output).
7: Undertorque detection only
with speed agreement; output
stopped upon detection.
8: Undertorque detected continu-
ously during operation; output
stopped upon detection.
Inverter rated current is set as
100%.
Sets the overtorque/undertorque
detection time.
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 8
6
No
A
0 to
15%
No
A
300
0.0 to
10.0 s
No
A
10.0
MEMO-
BUS
Page
Register
4A1H
6-30
4A2H
6-30
4A3H
6-30