Auto Restart External Outputs
To output auto restart signals externally, set H2-01 or H2-02 (multi-function contact output terminals M1-M2
or M3-M4 function selection) to 1E (auto restart).
Related Parameters
Param-
eter
Name
Number
Number of auto restart
L5-01
attempts
Auto restart operation selec-
L5-02
tion
L5-03
Fault Retry Time
Application Precautions
The number of auto restarts counter is reset under the following conditions:
After auto restart, normal operation has continued for 10 minutes.
•
After the protection operation has been performed and an error reset has been input.
•
After the power supply is turned OFF, and then ON again.
•
Description
Sets the number of auto restart attempts.
Automatically restarts after a fault and conducts a
speed search from the run frequency.
Sets whether a fault contact output is activated
during fault restart.
0: Not output (Fault contact is not activated.)
1: Output (Fault contact is activated.)
Sets the maximum time a restart is tried.