Auto Restart External Outputs
To output auto restart signals externally, set H2-01 or H2-02 (multi-function contact output terminals M1-M2
or M3-M4 function selection) to 1E (auto restart).
Related Parameters
Param-
eter
Name
Number
Number of auto restart
L5-01
attempts
Auto restart operation selec-
L5-02
tion
L5-03
Fault Retry Time
Application Precautions
The number of auto restarts counter is reset under the following conditions:
After auto restart, normal operation has continued for 10 minutes.
After the protection operation has been performed and an error reset has been input.
After the power supply is turned OFF, and then ON again.
Description
Sets the number of auto restart attempts.
Automatically restarts after a fault and conducts a
speed search from the run frequency.
Sets whether a fault contact output is activated
during fault restart.
0: Not output (Fault contact is not activated.)
1: Output (Fault contact is activated.)
Sets the maximum time a restart is tried.
Change
Setting
Factory
during
Access
Range
Setting
Opera-
Level
tion
0 to 10
0
No
A
0 or 1
0
No
A
0.5 to
10.0 s
No
A
180.0
6
45
6-