Omron VARISPEED E7 User Manual page 100

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Param-
eter
Name
Number
Sets the source of frequency refer-
ence for HAND operation.
HAND Fref
b1-12
0: Digital Operator
Source*
1: Control Circuit Terminal (ana-
log input)
* This parameter is effective only, if the HOA operator JVOP-162 is used.
DC Injection Braking: b2
Param-
eter
Name
Number
Used to set the frequency at which
DC injection braking starts in units
DC injection
of Hz when b1-03 is set to 0 (decel-
b2-01
braking starting
eration to stop).
frequency
When b2-01 is less than E1-09, E1-
09 becomes the DC injection brak-
ing starting frequency.
Sets the DC injection braking cur-
DC injection
b2-02
rent as a percentage of the inverter
braking current
rated current.
Used to set the time to perform DC
injection braking at start in units of
DC injection
1 second.
b2-03
braking time at
Used to stop coasting motor and
start
restart it. When the set value is 0,
DC injection braking at start is not
performed.
Used to set the time to perform DC
injection braking at stop in units of
DC injection
1 second.
b2-04
braking time at
Used to prevent coasting after the
stop
stop command is input. When the
set value is 0.00, DC injection
braking at stop is not performed.
Sets the DC current level when the
Motor pre-heat
b2-09
motor pre-heat function is enabled
current
using a digital input.
Setting
Description
Range
0 or 1
Setting
Description
Range
0.0 to
10.0
0 to
100
0.00
to
10.00
0.00
to
10.00
0 to
100
Change
MEMO-
Factory
during
Access
BUS
Setting
Opera-
Level
Register
tion
0
No
A
01E0
Change
MEMO-
Factory
during
Access
BUS
Setting
Opera-
Level
Register
tion
0.5 Hz
No
A
189H
50%
No
A
18AH
0.00 s
No
A
18BH
0.50 s
No
A
18CH
0%
No
A
1E1H
Page
Page
6-12
6-10
6-12
5
6-12
6-10
6-12
6-13
13
5-