Omron VARISPEED E7 User Manual page 115

Variable torque frequency inverter
Hide thumbs Also See for VARISPEED E7:
Table of Contents

Advertisement

Setting
Value
6
7
8
9
A
B
C
E
F
10
11
12
17
1A
1E
1F
20
5
38
39
3A
3B
Analog Inputs: H3
Parame-
ter Num-
ber
Gain (terminal
H3-02
A1)
Bias (terminal
H3-03
A1)
Multi-function
analog input ter-
H3-08
minal A2 signal
level selection
Multi-function
analog input ter-
H3-09
minal A2 func-
tion selection
Gain (terminal
H3-10
A2)
28
5-
Inverter operation ready
READY: After initialization or no faults
During DC bus undervoltage (UV) detection
During baseblock (NO contact, ON: during baseblock)
Frequency reference source selection (ON: Frequency reference from Operator)
Run command source selection status (ON: Run command from Operator)
Overtorque/undertorque detection 1 NO (NO contact, ON: Overtorque/undertorque detection)
Loss of frequency reference (Effective when 1 is set for L4-05)
Fault (ON: Digital Operator communications error or fault other than CPF00 and CPF01 has
occurred.)
Not used. (Set when the terminal is not used.)
Minor fault (ON: Alarm displayed)
Fault reset command active
Timer function output
Overtorque/undertorque detection 1 NC (NC Contact, OFF: Torque detection)
Reverse direction
Restart enabled (ON: Restart enabled)
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)
OH pre-alarm (temperature reached L8-02)
Drive enabled
Drive waiting (start delay time b1-11 is active)
During OH and reduced Frequency
RUN command from option card/communications
Name
Description
Sets the frequency as a percent-
age of the maximum output fre-
quency, when 10 V is input.
Sets the frequency as a percent-
age of the maximum frequency,
when 0 V is input.
0: 0 to +10V (11 bit).
2: 4 to 20 mA (9-bit input).
3: 0 to 20 mA (9-bit input)
Switch current and voltage input
using the switch S1 on the control
terminal board.
Selects the multi-function analog
input function for terminal A2.
Refer to the table on the next
page.
Sets the input level when terminal
A2 input is 10 V (20 mA) accord-
ing to the 100% value of the func-
tion set in parameter H3-09.
Function
Change
Setting
Factory
during
Range
Setting
Opera-
tion
0.0 to
100.0%
Yes
1000.0
-100.0
to
0.0%
Yes
+100.0
0, 2, 3
2
No
0 to 16
0
No
0.0 to
100.0%
Yes
1000.0
Page
6-62
6-62
6-62
6-62
6-62
6-30
6-43
6-62
-
6-62
6-63
6-83
6-30
6-63
6-45
6-32
6-63
6-63
6-63
6-63
6-63
MEMO-
Access
BUS
Page
Level
Register
A
411H
6-21
A
412H
6-21
A
417H
6-21
A
418H
6-21
A
419H
6-21