Type Of Protected Object; Normal Operational Status; System Frequency; Motor/Generator Information - Siemens 7UT51 Instruction Manual

Protective relay
Hide thumbs Also See for 7UT51:
Table of Contents

Advertisement

5
Motor or Generator Differential Protection (87M/G)
5.2.1

Type of Protected Object

The relay uses different settings and algorithms for
different types of protected objects. Address 7801
specifies what type of device or equipment is being
protected.
7801 PROT.OBJ
Type of object the relay is protecting.
Option
Description
-
-
2
WIND
TRANSF
two
(see Chapter 4)
-
-
3
WIND
TRANSF
three
(see Chapter 4)
MOTOR/
motor or generator
GENERATOR
2 ENDED TIE PT.
two
3 ENDEDTIE PT.
three
-
1Ph.
TRANSF
single
(see Chapter 4)
Model 7UT513 is required (instead of a 7UT512) only
if the application includes measurement of a ground
(or neutral) current. A 7UT513 can also be used to
protect simultaneously both a motor/generator and an
additional protected device.
5.2.2

Normal Operational Status

The 87M/G differential function can be set either to
exist (ENABLED) or not exist. The choice is made in
Address 7816.
7816 87 STATUS
Choice of whether motor/generator differential
protection function (87M/G) exists.
Option
Description
EXISTENT
87M/G function exists (default).
NONEXISTENT
87M/G function does not exist.
Once the 87M/G function is set to exist, it can be
configured. Its normal status is set in Address 1701.
1701 87 STATUS
Operational status of differential protection (87M/G)
when the protected object is a motor or generator.
Option
Description
OFF
87M/G function is inactive (default).
ON
87M/G function is active.
68
-
winding transformer (default)
-
winding transformer
-
branch bus (see Chapter 6)
-
branch bus (see Chapter 6)
-
phase transformer
1701 87 STATUS
Operational status of differential protection (87M/G)
when the protected object is a motor or generator.
BLOCK
87M/G function is active except that trip
TRIPPING
contacts and signal contacts will not
respond to 87M/G events.
5.2.3

System Frequency

The rated nominal frequency of the protected
equipment is specified in Address 7899.
7899 FREQUENCY
Rated nominal frequency of the protected motor/
generator.
Option
FREQ 50 Hz
FREQ 60 Hz
FREQ 16 2/3 Hz
Note: The choice of frequency affects the availability
the auxiliary protection functions. With rated
frequency 60Hz, the backup overcurrent time
protection or the restricted earth fault
protection/tank leakage protection (dependent
on the ordered model) can be used besides the
differential protection for the motor/generator.
With rated frequency 50Hz, the backup overcurrent
time protection or the restricted earth fault protection/
tank leakage protection (dependent on the ordered
model) can be used besides the differential protection
for the motor/generator.
With rated frequency 16 2/3 Hz, no restriction
concerning the additional functions are present.
5.2.4
Motor/Generator
Information
The phase-to-phase voltage and rated apparent
power of the protected motor/generator is specified in
Addresses 1202 and 1203. The relay automatically
calculates the primary measured values based on this
information.
1202 Vn M/G
-
-
Rated phase
to
phase voltage of the motor or
generator
Range: 0.4
800.0 kV
Default: 21.0
7UT51 v3
Description
50 Hertz
60 Hertz (default)
-
16
2/3 Hertz
PRIM-2330C