4 Technical Data
4.1.7

Climatic Stress Tests

1
Temperatures
)
Humidity
4.1.8

Deployment Conditions

304
Standards:
Type tested (acc. IEC 60086-2-1 and -2, Test
Bd, for 16 h)
admissible temporary operating temperature
(tested for 96 h)
recommended for permanent operation (ac-
cording to
IEC 60255–6)
Limit temperatures for storage
Limit temperatures during transport
Storage and transport of the device with factory packaging!
1
) UL–certified according to Standard 508 (Industrial Control Equipment):
Limit temperatures for normal operation (i.e.
output relays not energized)
Limit temperatures under maximum load
(max. cont. admissible input and output
values)
admissible humidity
Siemens recommends that all devices be installed so that they are not exposed to direct sun-
light nor subject to large fluctuations in temperature that may cause condensation to occur.
The protection device is designed for installation in normal relay rooms and plants, so that elec-
tromagnetic compatibility (EMC) is ensured if installation is done properly.
In addition the following is recommended:
• Contacts and relays operating within the same cabinet or on the same relay board with
digital protection equipment, should be in principle provided with suitable fuses.
• For substations with operating voltages of 100 kV and above, all external cables should be
shielded with a conductive shield grounded at both ends. Normally in medium voltage
systems no special procedures are necessary.
• Do not withdraw or insert individual modules/boards while the protective device is ener-
gized. In withdrawn condition, some components are electrostatically endangered; during
handling the ESD standards (for Electrostatic Sensitive Devices) must be observed. They
are not endangered when inserted into the case.
IEC 60255-6
–25 °C to +85 °C / –13 °F to +185 °F
– 4.00 °F to +158.00 °F / –20 °C to +70 °C (legi-
bility of display may be restricted from +131.00
°F / +55 °C)
-5 °C to +55 °C / +23 °F to +131 °F
–25 °C to +55 °C / –13 °F to +131 °F
–25 °C to +70 °C / –13 °F to +158 °F
-20 °C to +70 °C / –4 °F to +158 °F
-5 °C to +55 °C / +23 °F to +131 °F
annual average ≤ 75 % relative humidity;
on 56 days of the year up to 93% relative humid-
ity. CONDENSATION MUST BE AVOIDED IN
OPERATION