Boost Of Room Temperature Setpoint (Dtrsa); Boost Heating - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Note
Setting
Effect
Siemens Building Technologies
Landis & Staefa Division
3.14
Boost of room temperature setpoint
(DTRSA)
Reduction of the building's heating up time.
This setting is active only if a room sensor is used.
Setting range
0...20
The duration of boost heating will be changed.
Entry:
Increase:
More setpoint boost
Heating up time will become shorter
Decrease:
Less setpoint boost
Heating up time will become longer
3.14.1

Boost heating

Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
With the setting on line 33
room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.
°C
TR
w
20
15
a
TRx
Actual value of the room temperature
TRw
Room temperature setpoint
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C (K)
, the room temperature setpoint will be raised until the
OEM
TR
x
b
33
OEM
t
Factory setting
5
t
etpoint boost
Time
145/184
CE1P2374E
19.04.2001

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents