Boost Of Room Temperature Setpoint - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Benefit
 Note
Setting
Effect
Boost heating
Siemens Building Technologies
HVAC Products

5.51 Boost of room temperature setpoint

• Reduction of the room's heating up time
Boosts the room temperature setpoint temporarily, aimed at achieving shorter heating
up times for the room. This setting is active only if a room temperature sensor is used.
Setting range
0...20
The duration of boost heating will be changed.
Entry:
Increase:
More setpoint boost
Heating up time will become shorter
Decrease:
Less setpoint boost
Heating up time will become longer
Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
The room temperature setpoint will be raised by the setting made on line 703
the room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.
°C
TR
w
TRN
20
TRR
15
TRx
Actual value of the room temperature
TRw Room temperature setpoint
TRN Nominal room temperature setpoint
TRR Reduced room temperature setpoint
Basic Documentation RVP540 / RVP550
Description of the EXP settings
Unit
K
TR
x
a
b
703
EXP
t
Factory setting
5
EXP
t
Boost of room temperature setpoint
Time
CE1P2488en
until
311/348
18.10.2002