3.9.3

Temperature-time integral

The temperature-time integral generates the locking signal for restricting the heating
circuits.
During the generation of the locking signal, the following processes can take place:
Diagram
Procedure
a to b
Within a foreseeable period of time, the actual boiler temperature (TKx)
will lie below the value of Tkmin-SDK/2.
è
è
è
è
b to c and
Within a foreseeable period of time, the actual boiler return temperature
d to e
(TKx) will lie within half the switching differential of the boiler return
temperature's minimum limitation.
è
è
è
è
c to d and
Within a foreseeable period of time, the actual boiler return temperature
e to f
(TKx) will lie above TKw.
è
è
è
è
TK
TKx
SDK/2
TKmin
y
x%
0%
a
TK
boiler temperature
TKx
Actual value of boiler temperature
Tkmin Minimum limitation of boiler temperature
SDK
Boiler switching differential (factory setting = 8K)
t
Time
Y
Locking signal
Basic Dokumentation RVA63.280, RVA53.280
Locking signal will be built up
Locking signal will remain at a constant level
Locking signal will be decreased
b
c
d
t
t
e
f
CE1P2374E