Floor curing

The floor curing function ensures controlled drying of the floor.
Observe the relevant standards and regulations of the floor manufacturer!
Proper functioning is ensured only when the plant is correctly installed (hydraulic
system, electrical installation, settings)!
If not observed, the floor might get damaged!
The floor curing function maintains the flow temperature at a predefined temperature
profile with the help of the mixing valve.
Setting range
0...3
Selection of a temperature profile activates the floor curing function and the heating
circuit ensures the preset flow temperatures.
0
Inactive
1
Functional heating
2
Floor curing heating
3
Functional and floor curing heating
2.35.1

Temperature profile

The following graph shows the temperature profile of the selected floor curing function.
[TVw]
55
50
45
40
35
30
25
20
0
1
5
7
X
Fh
1
TVw
Flow temperature setpoint
x
Start day
Fh
Functional heating
Bh
Floor curing heating
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
1
5
10
Bh
Fh + Bh
Factory setting
0
15
18
[Tag
]
25
CE1P2374E