Central Stand-By Switch - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Important
Effect
Important
D.h.w.
Display
118/184
Siemens Building Technologies
Landis & Staefa Division
2.50

Central stand-by switch

Central operation in the selected range of action.
From the master controller, the heating system can be switched to stand-by in the
selected range of action.
Setting range
0 / 1
This setting can only be made on the master controller (device with setting on
line 140 = 1) and the setting line will only be displayed on this controller!
Entry:
0
central stand-by circuit is switched off
1
central stand-by circuit is activated
Segment address
0
1...14
If central stand-by on the master controller is switched on, it can only be switched off
again from that controller!
The central stand-by circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.
If the central stand-by circuit is activated, the stand-by button
selected range of action flashes.
Basic Dokumentation RVA63.280, RVA53.280
Unit
Increment
Effect
According to the setting made on
line 145
Throughout the segment
Factory setting
0
on all controllers in the
CE1P2374E
19.04.2001