Maintenance

1.26

Standard times

Straightforward resetting of all time switch programs to their standard values.
The standard time program resets the time settings of all time switch programs. For this
purpose, the controller is supplied with non-volatile factory settings.
Setting
The standard time program is activated as soon as the display changes to 1.
Display
0 / 1
In that case, the individual settings will be lost!
The time settings will be overwritten with the standard values. This applies to the
following settings:
• Only the switching times of time switch program 1 or 2
preselected with the heating circuit selection button will be
overwritten.
• The switching times of time switch program 3 (d.h.w.) will be
overwritten.
Switching point
Period 1 ON
Period 1 OFF
Period 2 ON
Period 2 OFF
Period 3 ON
Period 3 OFF
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
Setting line
6
-
7
-
8
-
9
-
10
-
11
-
Time switch program
1 or 2
-
...
...
Standard time
20
06 : 00
21
22 : 00
22
– – : – –
23
– – : – –
24
– – : – –
25
– – : – –
3
CE1P2374E
19.04.2001