5.24 Boost of room temperature setpoint (DTRSA)

Reduction of the building's heating up time.
This setting is active only if a room sensor is used.
Setting range
0...20
The duration of boost heating will be changed.
Entry:
Increase:
More setpoint boost
Heating up time will become shorter
Decrease:
Less setpoint boost
Heating up time will become longer

5.24.1 Boost heating

Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
With the setting on line 33
room is heated up (TRw - ¼ °C).
The boost produces an increase in the flow temperature setpoint.
°C
TR
w
20
15
a
TRx
Actual value of the room temperature
TRw
Room temperature setpoint
33
Setpoint boost
OEM
t
Time
Basic Documentation RVA63.242, RVA53.242
Description of OEM settings
Unit
°C (K)
, the room temperature setpoint will be raised until the
OEM
TR
x
b
Factory setting
5
t
CE1P2373E
26.03.2001