Operating mode of the boiler

A minimum boiler temperature is maintained only if required.
The setting defines whether it is necessary or desirable to maintain a minimum boiler
return temperature.
Setting range
0...2
The following settings are available:
0
Continuous operation:
The boiler operates at the minimum boiler temperature level (operating line 81),
independent of whether or not the consumers currently call for heat. Exception
Stand-by. Without extended burner running time.
1
Automatic operation:
The boiler is operated only when one of the consumers calls for heat. If the
demand for heat drops below TKmin, the boiler is still maintained at the minimum
boiler temperature level (operating line 81). Without extended burner running
time
2
Automatic operation:
The boiler is operated only when one of the consumers calls for heat. The
effective boiler temperature setpoint is used, even if it lies below TKmin
(operating line 81).
If the boiler temperature drops below the setpoint by half the boiler's switching
differential (SDK/2), the burner will be put into operation until the boiler
temperature has exceeded TKmin by one switching differential (extended burner
running time). With extended burner running time
Of course, if the demand for heat by one of the consumers exceeds the minimum boiler
temperature, the required setpoint will be maintained.
In stand-by mode
of all heating circuits, minimum limitation is deactivated. In that
case, the controller must be in "standalone" mode (device address 0). The boiler
temperature is maintained at required level only when there is demand for heat. The
protective functions will remain active, however.
3.8.1

Extended burner running time

Without extended burner running time
TK
°C
TKw
70
60
50
40
TKmin
30
20
10
0
20
10
0
-10
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
TAgem
-20 °C
Factory setting
2
With extended burner running time
TK
°C
TKw
70
60
50
TKmin
40
30
20
10
0
20
10
0
-10
-20 °C
TAgem
137/184
CE1P2374E
19.04.2001