Description Of End-User Settings; User Interface; Operating Modes Of Heating Circuit - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Note
Effect
36/184
Siemens Building Technologies
Landis & Staefa Division
1

Description of end-user settings

User interface

1.1

Operating modes of heating circuit

Straightforward and direct selection of heating circuit operating modes.
The control provides 3 different heating circuit operating modes that can be directly
selected as required.
Select the required operating mode by pressing the respective operating mode button.
It is located on the controller front for direct access by the user.
The setting can be made separately for both heating circuits with the heating circuit
selection button.
The d.h.w. operating mode will not be affected by the selected heating circuit operating
mode, with the exception of the holiday function and when the remote telephone switch
is activated
Operating
Designation
mode
Automatic
operation
Continuous
operation
Stand-by
Basic Dokumentation RVA63.280, RVA53.280
Effect of selected operating mode
• Heating according to the time program
(lines 5 to 11)
• Temperature setpoints according to the heating
program
• Protective functions active
• Changeover on the room unit active
• Automatic summer / winter changeover (ECO
functions) and automatic 24-hour heating limit
active
• Heating mode with no time program
• Temperature adjustment with the setpoint knob
• Protective functions active
• Changeover on room unit inactive
• Automatic summer / winter changeover (ECO
inactive
functions)
• Heating OFF
• Temperature according to frost protection
• Protective functions active
• Changeover on room unit inactive
• Automatic summer / winter changeover (ECO
functions) and automatic 24-hour heating limit
active
CE1P2374E
19.04.2001