With room influence

The automatic 24-hour heating limit operates depending on the current flow
temperature setpoint. If a room unit is connected, the room influence continuously
readjusts the flow temperature setpoint.
This means that the automatic 24-hour heating limit differs when room influence is
used.
The temperature basis used for this process are the values of the flow temperature
setpoint and the current room temperature setpoint.
If the flow temperature setpoint corrected by the room influence falls below the room
temperature setpoint plus a correction value, the heating will be switched off.
Heating's switch-off point:
TVwk
If the flow temperature setpoint corrected by the room influence exceeds the room
temperature setpoint plus a correction factor, the heating will be switched on.
Heating's switch-on point:
TVwk
TVwk
Flow temperature setpoint corrected by the room temperature
TRw
Room temperature setpoint
s
Slope of heating curve