Benefit
Description
Setting
Note
Effect
Reduction
Note
Adaption of heating
curve
Siemens Building Technologies
Landis & Staefa Division
3.20

Adaption sensitivity 1 (ZAF1)

Adaption of the heating curve as a function of the outside temperature.
Adaption sensitivity 1 serves for calculating the adaption of the heating curve in the
temperature range 4 to 12 °C. Also refer to "adaption of heating curve" in Index.
Setting range
1...15
The level of adaption sensitivity is automatically adapted by the controller and,
therefore, need not be manually adjusted.
The heating curve in the temperature range 4 to 12 °C will be differently adapted,
depending on the level of adaption sensitivity 1.
Increase:
More adaption
Decrease:
Less adaption
Each time a significant adaption of the heating curve between 4 and 12 °C (ZAF1) has
taken place, adaption sensitivity 1 will automatically be reduced by one step. This
means that the extent of adaption and thus the readjustment of the slope and the
heating curve's parallel displacement will gradually be reduced .
When readjusting the slope of the heating curve, the adaption sensitivity will
automatically be reset to the factory setting.
The process of heating curve adaption is described in the relevant section. Also refer to
"adaption of heating curve" in Index.
Basic Dokumentation RVA63.280, RVA53.280
Unit
-
Factory setting
15
151/184