Switching Differential Of The Boiler Temperature - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Boiler temperature
control
Switching differential
Siemens Building Technologies
Landis & Staefa Division
3.3
Switching differential of the boiler
temperature
Matching the burner to the type of boiler.
The boiler temperature is controlled by a 2-position controller for which a switching
differential can be set.
Setting range
0...20
The setting changes the switching differential of the boiler temperature control.
Entry:
Increase:
Switching differential will become wider
Fewer burner starts and longer burner running times
Decrease:
Switching differential will become smaller
More burner starts and shorter burner running times
With 2-position control, heat is produced at certain intervals. The period of time during
which heat is delivered is dependent upon the boiler mass and the amount of water
contained in the boiler.
The greater the demand for heat, the longer the burner runs at a time.
SD
ON
OFF
w
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C (K)
w
Setpoint
SD
Switching differential of the boiler
Switch-on point
Switch-off point
°C
Factory setting
8
131/184