Increasing The Economy Setpoint; Room Temperature Setpoint Adjuster, Absolute - Siemens Synco 700 Series Basic Documentation

Modular boiler sequence controller including extension modules rmz785, rmz787, rmz788 and rmz789
Hide thumbs Also See for Synco 700 Series:
Table of Contents

Advertisement

Settings
Display values
160/232
Building Technologies
HVAC Products

10.4.2 Increasing the Economy setpoint

The room temperature setpoint of Economy mode is increased depending on the
composite outside temperature. The increase is greater at low outside temperatures
and zero at high outside temperatures; the transitions are adjustable.
The function helps prevent peak loads when changing from Economy to Precomfort or
Comfort mode.
TRSetpt
TRSetptCmf
TRSetptPreC
TRSetptEco
–15°C
EndPt
EndPt
End point of increase (here –15 °C)
SrtPt
Start point of increase (here –5 °C)
Toeff
Composite (effectively acting) outside temperature
TRSetpt
Room temperature setpoint
TRSetptCmf
Comfort setpoint
TRSetptEco
Economy setpoint
TRSetptEco+ Δ Increased Economy setpoint
TRSetptPreC
Precomfort setpoint
TRSetptPreC+ Δ Increased Precomfort setpoint
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Economy increase start point
Economy increase end point
The Inputs/setpoints menu shows the extent of Economy setpoint increase:
Main menu > Heating circuit > Inputs/setpoints
Operating line
Economy increase

10.4.3 Room temperature setpoint adjuster, absolute

For preselection of the room temperature setpoints for Comfort and Precomfort mode, a
remote setpoint adjuster (e.g. BSG21.1) can be configured.
The 4 setpoints can be readjusted as shown in the following illustration.
The upper curve shows the difference between the remote setpoint adjuster's setpoint
and the selected Comfort setpoint. This difference affects the other setpoints in different
ways. This is shown by the curves in the lower part of the diagram.
Boiler Sequence Controller RMK770
10 Heating circuit control
TRSetptEco+Δ / TRSetptPreC+Δ
TRSetptEco+Δ
–5°C
SrtPt
Range
–15...50 °C
–50...–5 °C
Adjustable values / display / remarks
Inactive / Active
TOeff
Factory setting
–5 °C
–15 °C