Maximum Forward Shift Of Optimum Start Control; Optimum Start Control - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Siemens Building Technologies
Landis & Staefa Division
2.30
Maximum forward shift of optimum start
control

Maximum forward shift of optimum start control.

Maximum forward shift is a limit function that defines the range of optimum start control.
Setting range
00:00...06:00
00:00
Optimum start control switched off
00:10...06:00 Optimum start control switched on
2.30.1

Optimum start control

Optimum start control acts with or without room influence.
The maximum forward shift can be set with parameter "Maximum forward shift with
optimum start control" (range 0...6 h). This parameter can also be used to switch
optimum start control off (setting 0).
During non-occupancy hours, the heating is maintained at the reduced level. Towards
the end of the non-occupancy time, optimization switches the control back to the
normal level.
Optimization calculates the changeover time such that, at the start of occupancy, the
room temperature will have reached the nominal setpoint.
Basic Dokumentation RVA63.280, RVA53.280
Unit
hh:mm
Factory setting
00:00
91/184
CE1P2374E
19.04.2001

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents