P-band mixing valve (Xp)

Adapting the control characteristic to the plant's behavior (controlled system).
Setting the proportional band for control of mixing valve actuators Y1 and Y5 that can
be used for heating circuit 1 and heating circuit 2.
Setting range
1...100
Xp influences the controller's P-behavior.
3.23

Integral action time mixing valve (Tn)

Adapting the control characteristic to the plant's behavior (controlled system).
Setting the I-part for control of mixing valve actuators Y1 and Y5 that can be used for
heating circuit 1 and heating circuit 2.
Setting range
10...873
Tn influences the controller's I-behavior.
3.24

Actuator running time mixing valve

Setting the actuator running time.
Mixing valves have different actuator running times.
Setting range
30...873
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C (K)
Unit
s
Unit
s
Factory setting
32
Factory setting
120
Factory setting
120
153/184
CE1P2374E
19.04.2001