Without Room Influence; With Room Influence - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Parameter KON:
92/184
Siemens Building Technologies
Landis & Staefa Division
2.30.2

Without room influence

The composite outside temperature is used as the compensating variable. In the case
of floor heating systems, the maximum forward shift should be longer than with radiator
systems.
Using the parameter for the constant of quick setback and optimum start control (KON),
the forward shift can be matched the building dynamics.
Forward shift tE in hours and minutes with optimum start control without room
influence:
TAgem
KON
0
- 20
0
- 10
0
0
0
+ 10
0
tE
TAgem Composite outside temperature
tE
Forward shift
KON
Parameter for quick setback and optimum start control without room influence
KON = 0:
Small KON:
Large KON:
2.30.3

With room influence

Optimum start control acts only when room influence is active.
The switch-on time for the heating (change to nominal level) is selected such that, at
the beginning of the occupancy time according to the heating program, the room
temperature reached will be the room temperature setpoint - 0.25 K.
The correct switch-on time is determined by adaption.
Basic Dokumentation RVA63.280, RVA53.280
4
8
1h20
2h40
0h50
1h50
0h30
1h00
0
0h10
function deactivated
note: KON also acts on quick setback
for high building structures can be heated up fairly quickly
for heavy, well insulated building structures whose heating
up time is fairly long
12
16
4h00
5h20
2h40
3h40
1h30
2h00
0h10
0h20
20
6h00
4h30
2h30
0h20
CE1P2374E
19.04.2001