Maximum Forward Shift Of Optimum Stop Control; Optimum Stop Control - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Siemens Building Technologies
Landis & Staefa Division
2.31
Maximum forward shift of optimum stop
control

Maximum forward shift of optimum stop control.

Maximum forward shift is a limit function that defines the range of optimum stop control.
Setting range
00:00...06:00
00:00
Optimum stop control deactivated
00:10...06:00 Optimum stop control activated
2.31.1

Optimum stop control

Optimum stop control acts only when a room sensor is used and when room influence
is active.
The maximum forward shift can be set with parameter "Maximum forward shift with
optimum stop control" (range is 0...6 h). This parameter can also be used to switch
optimum stop control off (setting = 0).
During occupancy hours, the heating is maintained at the nominal level. Towards the
end of the occupancy time, the control switches to the reduced level.
Optimization calculates the changeover time such that, at the end of occupancy time,
the room temperature will be 0.5 °C below the nominal setpoint (early shut-down).
Adaption takes place only with the first occupancy period per day. The switch-off point
is adapted in steps of 10 minutes. If the 0.25 K are not reached, the switch-off point is
shifted forward by 10 minutes (earlier shut-down). In the other case, the switch-off point
is shifted backward by 10 minutes (later shut-down).
Basic Dokumentation RVA63.280, RVA53.280
Unit
hh:mm
Factory setting
00:00
93/184
CE1P2374E
19.04.2001

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rva53.280

Table of Contents