Minimum limitation of burner running time

Reduction of burner switching frequency.
Also termed "Burner cycling protection".
Setting range
0...10
Once switched on, burner stage 1 will remain activated for at least the period of time
set here.
As soon as the burner is switched on, the minimum burner running time starts to make
certain the burner will not be switched off before the set minimum time has elapsed.
Each time the burner is switched off, the minimum burner running time will be reset if
not yet elapsed.
If the boiler temperature exceeds the setpoint by the amount of the entire switching
differential, the minimum burner running time will be ignored for safety reasons
TK
°C
60
50
40
30
0
4
1
FZ
0
1
BR
0
BR
Burner
FZ
Release counter
SDK
Switching differential of the boiler
Basic Dokumentation RVA63.280, RVA53.280
Unit
min
TK
x
8
12
16
tBRmin
tBRmin Minimum burner running time
TKw
TKx
Factory setting
4
TKw
+SDK
TKw
+SDK/2
TKw
TKw-
SDK/2
20
min
t
Boiler temperature setpoint
Actual value of boiler temperature
133/184
CE1P2374E
19.04.2001