Siemens RVA63.280 Basic Documentation page 19

Boiler and heating circuit controllers
Table of Contents

Advertisement

Input test
Note
Siemens Building Technologies
Landis & Staefa Division
Buttons
Explanation
1
Press one of the line selection buttons.
This will take you to the programming mode.
2
Press both line selection buttons for at least 3
seconds.
This will take you to the programming mode "Heating
engineer".
3
Press line selection button UP until you reach line 52.
-
This will take you to the input test.
4
Press the + or - button repeatedly, which will take you
one test step further:
Test step 0
Test step 1
Test step 2
Test step 3
Test step 4
Test step 5
Test step 6
Test step 7
Test step 8
Test step 9
5
By pressing any of the operating mode buttons, you
leave the programming mode and thus the input test.
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
The selected sensor values are updated within a maximum of 5 seconds.
An open-circuit is displayed as – – –.
A short-circuit is displayed as o o o.
Basic Dokumentation RVA63.280, RVA53.280
Display of boiler temperature acquired with sensor
B2
Display of d.h.w. temperature acquired with sensor
B3
Display of input B31/H2/B41 according to the
function selected on line 174 [°C or ooo or ---].
Display of flow temperature HC1 acquired with
detector B1
Display of flow temperature HC2 acquired with
detector B12
Display of outside temperature acquired with
sensor B9
Display of room temperature acquired with room
unit connected to A6
Display of room temperature acquired with room
unit connected to A7
Display of the flue gas temperature acquired with
sensor B8
Display of input H1 according to the function
selected on line 170 [°C / 000 / - - -].
Line
Continuous
display
19/184
CE1P2374E
19.04.2001