Siemens Building Technologies
Landis & Staefa Division
1.12
Switching times of time switch programs 1
and 2
This is the setting of the switching times of time switch program at which the
temperature setpoints for the relevant heating circuit will change.
The heating program thus set becomes active with automatic mode
Setting range
- -:- -...24:00
First, select the weekday for which the switching times shall be entered!
The controller then makes a check to ensure the entries have been made in the correct
order.
At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:
– – : – –
Switching point inactive
00:00...24:00 At the time entered, heating to the respective temperature is ensured.
Line
Switching point
Switch-on time period 1
Switch-off time period 1
Switch-on time period 2
Switch-off time period 2
Switch-on time period 3
Switch-off time period 3
In AUTO mode, the time switch program can be set on both the controller (as described
above) and on the QAA70 room unit. It is always the last action that is active.
Basic Dokumentation RVA63.280, RVA53.280
Unit
h : min
Temperature setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
Setpoint of knob
Reduced setpoint
.
Factory setting
See "Program overview"
below
Standard
06:00
22:00
– – : – –
– – : – –
– – : – –
– – : – –
CE1P2374E
19.04.2001