Boost Of Flow Temperature Setpoint For D.h.w. Heating (Uebw) - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

Benefit
Description
Setting
Effect
Boiler boost
Note
Siemens Building Technologies
Landis & Staefa Division
2.41
Boost of flow temperature setpoint for
d.h.w. heating (UEBW)
Efficient d.h.w. heating.
To allow the d.h.w. to be heated up, the boiler temperature must be higher than the
d.h.w. setpoint.
Setting range
0...30
The setting will raise the boiler temperature setpoint when there is demand for d.h.w.
Increase:
Heating up time will become shorter
More overshoot
Decrease:
Heating up time will become longer
Less overshoot
Using the two settings, the controller generates the boiler temperature setpoint for
d.h.w. heating.
Setting on line 26
Setting on line 126
Total
For d.h.w. control, refer to "switching differential of d.h.w." in index.
Basic Dokumentation RVA63.280, RVA53.280
Unit
°C (K)
Reduced setpoint of d.h.w.
temperature
Boost
Boiler temperature setpoint
Factory setting
16