value, the lowering of the flow temperature setpoint will be gradually reduced. The
function operates with I-control action and an adjustable integral action time Tn.
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit > Controller
Operating line
[Tn] return temp limitation max
Minimum limitation of the return temperature uses a fixed integral action time.

10.4.3 Room temperature setpoint adjuster, absolute

For the preselected room temperature setpoints, Comfort and Precomfort, a remote
setpoint adjuster (e.g. BSG21.1) can be configured.
The 4 setpoints will be readjusted according to the following diagram.
0 K
SpCHCmf
z.B.:
SpCPrt
32 °C
SpCEco
28 °C
25 °C
SpCPreC
23 °C
SpCCmf
21 °C
SpHCmf
19 °C
SpHPreC
16 °C
SpHEco
12 °C
SpHPrt
C
Cooling
Cmf
Comfort
Eco
Economy
H
Heating
The input is activated via the extra configuration:
Main menu > Commissioning > Extra configuration > Heating circuit > Inputs >
Room setpoint adjuster abs
There are no settings required.
It is not recommended to use a QAA25 room temperature setpoint adjuster since its
characteristic is not linear so that setpoint deviations of maximum 1 K would occur.
Compensation is not possible.
The adjusted setpoint represents the Comfort setpoint. At the same time, the Precomfort
setpoint is displaced parallel, which means that the difference between the 2 setpoints will
be maintained.
Boiler Sequence Controller RMK770
10 Heating circuit control
Range
0...60 min
+10 K
0 K
-10 K
0.5 K
PreC Precomfort
Prt
Protection
SP
Setpoint
Assign terminal
Factory setting
30 min
0 K
CE1P3132en
01.03.2005