Operational Faults - Siemens RVA63.280 Basic Documentation

Boiler and heating circuit controllers
Table of Contents

Advertisement

34/184
Siemens Building Technologies
Landis & Staefa Division
2.8

Operational faults

2.8.1.1
No display on the controller:
• Is the heating plant's main switch turned on?
• Are the fuses in order?
• Check wiring
2.8.1.2
Heating control does not function. There is no display of the time of
day, or the time displayed is incorrect
• Check fuses of the plant
• Make a reset: Isolate controller from the mains supply for about 5 seconds (e.g. turn
off the boiler's main switch for 5 seconds)
• Set the correct time of day on the controller (operating line 1).
• Check the time of day on the clock time master if the controller is used in a system
2.8.1.3
Controlling element does not open / close or does not operate
correctly.
• Manual lever of controlling element may not be engaged
• Wiring to the controlling element interrupted (output test)
• Check wiring of the sensors (input test)
• Quick setback or automatic 24-hour heating limit is active
• Check the settings, especially the selection of the double function
2.8.1.4
Heating circuit pump does not run
• Is the right type of plant displayed (setting line 53)?
• Check wiring and fuse (output test)
• Check wiring of the sensors (input test)
• Check the settings, especially the selection of the double function
2.8.1.5
Burner does not switch on
• Press burner's reset button
• Check the fuses
• Wiring to the controlling element interrupted (output test)
• Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
• Quick setback or automatic 24-hour heating limit is active
• Check wiring of the boiler temperature sensor (input test)
2.8.1.6
Pump does not run
• Check wiring and fuse (output test)
• Check wiring of the sensors (input test)
2.8.1.7
D.h.w. is not being heated
• Has the button for d.h.w. heating been activated?
• Check setting of the electromechanical control thermostat (TR) installed on the
boiler. It must be above the TKmax setting
• Check setpoint of the d.h.w. temperature
• Check actual value of the d.h.w. temperature
Basic Dokumentation RVA63.280, RVA53.280
CE1P2374E