CHAPTER 16

Grounding the SRX550 Services Gateway

IN THIS CHAPTER

SRX550 Services Gateway Grounding Specifications | 76

Grounding the SRX550 Services Gateway | 77
SRX550 Services Gateway Grounding Specifications
To meet safety and electromagnetic interference (EMI) requirements and to ensure proper operation, the
SRX550 Services Gateway must be adequately grounded before power is connected. You must provide
a grounding lug to connect the services gateway to earth ground.
WARNING:
attach a cable lug to the grounding and power cables that you supply. A cable with an
incorrectly attached lug can damage the services gateway (for example, by causing a
short circuit).
To ground the services gateway before connecting power, you connect the grounding cable to earth ground
and then attach the lug on the cable to the chassis grounding point, using the screw.
Table 24 on page 76
lists the specifications of the grounding cable used with the device.
Table 24: Grounding Cable Specifications for the SRX550 Services Gateway
Grounding Requirement
Grounding cable
Amperage of grounding cable
Grounding lug
Before services gateway installation begins, a licensed electrician must
Specification
14 AWG single-strand wire cable
Up to 25A
Ring-type, Panduit LCC6-10A-L lug, or equivalent
76