Parameter, Control Data, Monitor Data And Table Information - Mitsubishi FX3U-20SSC-H User Manual

Hide thumbs Also See for FX3U-20SSC-H:
Table of Contents

Advertisement

FX
-20SSC-H Positioning Block User's Manual
3U
9.13

Parameter, Control Data, Monitor Data and Table Information

Item
Positioning Parameters
Ring counter setting
(Ver.1.10 or later)
Sudden stop selection
(STOP command)
(Ver.1.20 or later)
Sudden stop selection
Operation
(software limit)
parameters 2
(Ver.1.20 or later)
Sudden stop selection
(PLC limit)
(Ver.1.20 or later)
Sudden stop selection
(Servo amplifier limit)
(Ver.1.20 or later)
Maximum speed
Acceleration time
Deceleration time
Interpolation time constant
Ring counter upper limit value
(Ver.1.10 or later)
Sudden stop deceleration time
(Ver.1.20 or later)
Sudden stop interpolation time constant
(Ver.1.20 or later)
Positioning completion signal output waiting
time
(Ver.1.20 or later)
Monitor data
Current address (user)
Current address (pulse)
Real current address (user)
(Ver.1.20 or later)
Real current address (pulse)
(Ver.1.20 or later)
Received target address
(Ver.1.20 or later)
Received target speed
(Ver.1.20 or later)
Positioning parameter
Status
change completion flag
information 2
(Ver.1.20 or later)
Control data
Target address 1
Operation speed 1
Target address 2
Operation speed 2
Override setting
X-axis
BFM #14002 b3
BFM #14002 b4
BFM #14002 b5
BFM #14002 b6
BFM #14002 b7
BFM #14009,#14008
BFM #14018
BFM #14020
BFM #14022
BFM #14101, #14100 BFM #14301, #14300
BFM #14102
BFM #14104
BFM #14106
BFM #1,#0
BFM #3,#2
BFM #21,#20
BFM #23,#22
*2
BFM #25,#24
BFM #27,#26
BFM #32 b0
BFM #501,#500
BFM #503,#502
BFM #505,#504
BFM #507,#506
BFM #508
9.13 Parameter, Control Data, Monitor Data and Table
BFM Number
Y-axis
OFF :Disables the ring operation.
BFM #14202 b3
ON :Enables the ring operation.
OFF : Normal deceleration stop
BFM #14202 b4
ON : Sudden stop
OFF : Normal deceleration stop
BFM #14202 b5
ON : Sudden stop
OFF : Normal deceleration stop
BFM #14202 b6
ON : Sudden stop
OFF : Normal deceleration stop
BFM #14202 b7
ON : Sudden stop
Setting range:
BFM #14209,#14208
1 to 2,147,483,647 (user unit)
BFM #14218
BFM #14220
Setting range: 1 to 5000 ms
BFM #14222
Setting range:
1 to 2,147,483,646 (user unit)
BFM #14302
Setting range: 1 to 5000 ms
BFM #14304
Setting range: 1 to 5000 ms
BFM #14306
Setting range: 0 to 5000 ms
BFM #101,#100
Unit: user unit
BFM #103,#102
Unit: PLS
BFM #121,#120
Unit: user unit
BFM #123,#122
Unit: PLS
BFM #125,#124
Unit: user unit
BFM #127,#126
Unit: user unit
OFF : Positioning parameter change
BFM #132 b0
ON : Positioning parameter change
Setting range:
-2,147,483,648 to 2,147,483,647
BFM #601,#600
(user unit)
Setting range:
BFM #603,#602
1 to 2,147,483,647 (user unit)
Setting range:
-2,147,483,648 to 2,147,483,647
BFM #605,#604
(user unit)
Setting range:
BFM #607,#606
1 to 2,147,483,647 (user unit)
BFM #608
Setting range: 1 to 30000(x 0.1%)
9 Positioning Control
Description
*1
*1
*1
*1
*1
*1
not completed
completed
*1
*1 *3
*1
*1 *3
103
1
2
3
4
5
6
7
8
9
10