Omron e5ck User Manual page 97

Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

Cooling coefficient
• In heating and cooling control, P at the cooling side is calculated by the following for
mula:
Cooling side P = Cooling coefficient x P
Function
Setting
F Related description
4.1 Selecting the Control Method/Heating and cooling control (page 4 2)
F Related parameter
See
Proportional band" (level 1 mode)
Dead band
• Sets the output dead band width in a heating and cooling control system. A negative
setting sets an overlap band.
Function
Setting
F Related description
4.1 Selecting the Control Method/Heating and cooling control (page 4 2)
See
Setting Range
0.01 to 99.99
Setting Range
-19.99 to 99.99
Level 1 Mode
Conditions of Use
The control must be either heating and
cooling control, or advanced PID control.
Unit
None
Conditions of Use
The control system must be heating and
cooling control.
Unit
%FS
Default
1.00
Default
0.00
5–19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents