Omron e5ck User Manual page 121

Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

Automatic return of display mode
• If you do not operate any of the controller keys for the time set in this parameter when
in levels 0 to 2 and program modes, the display automatically returns to the PV/Pres
ent SP display.
Function
• When this parameter is set to 0", this function is disabled. (That is, the display does
not automatically return to the PV/Present SP display.)
• This parameter is disabled while the menu display is displayed.
Setting Range
Setting
AT hysteresis
• Normally, use the factory setting.
• The levels of limit cycle operations during AT execution are given hysteresis at event
ON/OFF switching. This parameter sets this hysteresis width.
Function
Setting Range
Setting
LBA detection width
• This parameter can be used when LBA is assigned as an output.
• When the change width of the manipulated variable is below the width set in this
parameter, the controller regards this as detection of an LBA.
Function
Setting Range
0.0 to 999.9
Setting
0 to 99
Second
0.1 to 9.9
Unit
%FS
Expansion Mode
Unit
Default
0
Conditions of Use
The control must be advanced PID con-
trol.
Unit
Default
%FS
0.2
Conditions of Use
The LBA (Loop Break Alarm) function
must be assigned as an output.
Default
0.2
5–43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents