MV upper limit
MV lower limit
MV change rate limit
• The MV upper limit" and MV lower limit" parameters set the upper and lower lim
its of the manipulated variable. When the manipulated variable calculated by the
E5CK T controller strays from the upper and lower limit range, the upper limit or
Function
lower limit set to these parameters is output, respectively.
• The MV change rate limit" parameter sets the maximum permissible change width
per second of the manipulated variable. If a change in the manipulated variable
causes this parameter setting to be exceeded, the calculated value is reached while
changing the value by the per second value set in this parameter.
This function is disabled when the set value is 0.0".
• MV upper limit
The setting ranges during standard control and heating and cooling control are dif
ferent.
Setting
Control Method
Standard
Heating and cooling
The manipulated variable at the cooling side during heating and cooling control is
expressed as a negative value.
• MV lower limit
The setting ranges during standard control and heating and cooling control are dif
ferent.
Control Method
Standard
Heating and cooling
The manipulated variable at the cooling side during heating and cooling control is
expressed as a negative value.
• MV change rate limit
Setting Range
0.0 to 100.0
F Related description
4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4 7)
See
Conditions of Use
The control must be advanced PID con-
trol.
Setting Range
MV lower limit +0.1 to 105.0
0.0 to 105.0
Setting Range
-5.0 to MV upper limit -0.1
-105.0 to 0.0
Unit
Default
%/S
0.0
Level 2 Mode
Unit
Default
%
105.0
%
105.0
Unit
Default
%
-5.0
%
-105.0
5–25