Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

Parameter No.
57
Input type
59
Scaling upper limit
58
Scaling lower limit
60
Decimal point
_C/_F selection
30
61
Control output 1 assignment
62
Control output 2 assignment
63
Auxiliary output 1 assignment
65
Alarm 1 type
66
Alarm 1 open in alarm
67
Alarm 2 type
68
Alarm 2 open in alarm
69
Alarm 3 type
70
Alarm 3 open in alarm
71
Direct/Reverse operation
28
Set point upper limit *1
27
Set point lower limit *1
72
PID / ON/OFF
α
35
85
AT calculated gain
36
Automatic return of display mode
93
AT hysteresis
55
LBA detection width
*7 See page 5 29.
*8 0: Control output (heat), 1: Control output (cool), 2 to 4: Alarms 1 to 3, 6: LBA, 7 and 8: Errors 1 to 2, 10 to 11: Time signal 1 to 2, 12:
Program end, 13: Stage output
*9 See page 5 34.
*10 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit values.
Parameter
6.4 Commands and Responses
Data Setting Range
0 to 21
Scaling lower limit +1 to 9999
-1999 to scaling upper limit -1
0 to 3
0: _C, 1: _F
0 to 4, 6, 10 to 13
0 to 4, 6, 10 to 13
2 to 4, 6 to 8, 10 to 13
1 to 11
0: Closed in alarm, 1: Open in alarm
1 to 11
0: Closed in alarm, 1: Open in alarm
1 to 11
0: Closed in alarm, 1: Open in alarm
0: Reverse operation, 1: Direct operation
Set point lower limit +1 to scaling upper limit
Scaling lower limit to Set point upper limit -1
0: Advanced PID, 1: ON/OFF
0.00 to 1.00
0.1 to 10.0
0 to 99
0.1 to 9.9
0.0 to 999.9
Mode
*7
*8
*8
*8
Set up
Set up
*9
*9
*9
Expansion
Expansion
6–9