Set point upper limit
Set point lower limit
• Limits the upper and lower limits when the SP is set. The SP can be set within the
range defined by the upper and lower limit set values of the set point upper limit"
and set point lower limit " parameters. Note that as these parameters are reset, the
Function
SP of existing settings that are out of the range are forcibly changed to one of the
upper or lower limit values.
• When the temperature input type and temperature unit have been changed, the set
point upper limit and set point lower limit are forcibly changed to the upper and
lower limits of the sensor.
• During temperature input, the decimal point position is dependent on the currently
selected sensor, and during analog input on the results of scaling.
Set point upper limit
Set point lower limit
Setting
During temperature input, the range becomes the range of use of the selected sensor
instead of the range defined by the scaling upper and lower limit values.
F Related description
4.2 Operating Condition Restrictions (page 4 7)
F Related parameter
See
Input type" Scaling upper limit" Scaling lower limit" Decimal point" (setup
mode)
PID/ON/OFF
• Selects advanced PID control or ON/OFF control.
Function
"
Setting
F Related description
4.1 Selecting the Control Method/ON/OFF control (page 4 5)
F Related parameters
See
Hysteresis (heat)" Hysteresis (cool)" (level 1 mode)
Parameter
Set point lower limit +1 to scaling upper limit
Scaling lower limit to set point upper limit -1
Setting Range
" :Advance PID/ "
" :ON/OFF
Expansion Mode
Setting Range
Default
Unit
Default
EU
1300
EU
-200
5–37