Omron e5ck User Manual page 53

Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

JManual operation
Manipulated variable (%)
Balance-less,
Bump-less Opera-
tion
• The manipulated variable is controlled manually.
• To set manual operation and manually set the manipulated variable,
press the
controller enters the manual mode. To quit the manual mode, press the
and
controller enters the level 0 mode without entering the menu display.
• Though the control shifts to manual operation if the controller is set to
the manual mode during program operation, the program advances.
When program operation is started in the manual mode, program also
advances.
• In the manual mode, the automatic return of display mode does not
work.
• Auto/manual can be switched up to 100,000 times.
• The process value is displayed on the No.1 display, and the manipulated
variable is displayed on the No.2 display.
• To change the manipulated variable, press the
two seconds, the manipulated variable is updated to the new setting.
• When switching between manual and auto operation, the manipulated
variable is subject to balance less, bump less operation.
• If the power is interrupted during manual operation, manual operation
is resumed at the manipulated variable that was active at power inter
ruption when the power is reset.
0
Manipulated vari-
able switched
Manual
Auto
+
To prevent sudden changes in the manipulated variable when switching between
manual and auto operation, operation is resumed using the value that was active im
mediately before operation was switched, and the value is brought gradually closer
to the value immediately after operation was switched.
3.8 Adjusting Control Operation
and
keys simultaneously for 1 second minimum. The
keys simultaneously again for 1 second minimum. The
Balance-less,
bump-less points
OFF
ON
Power inter-
ruption
or
keys. After
Time
+