Omron e5ck User Manual page 90

Digital controller (programmable type)
Hide thumbs Also See for e5ck:
Table of Contents

Advertisement

CHAPTER 5 PARAMETERS
Program Mode
Number of steps
• Specifies the number of steps in the current pattern.
Function
Setting
F Related description
3.5 Setting Patterns (page 3 14)
F Related parameter
See
All parameters in the program mode
Step 0 time (Step time)
Target SP 0 (Rate of rise programming)
Step 7 SP (Step time)
Target SP 7 (Rate of rise programming)
Step 8 SP (Step time)
Step 15 SP (Step time)
• Sets the SP of steps 0 to 15 when the step time is set.
• Sets target SP 0 to 7 when the rate of rise programming is set.
• During temperature input, the decimal point position is dependent on the currently
Function
selected sensor, and during analog input on the results of scaling.
Setting
F Related description
3.5 Setting Patterns (page 3 14)
4.3 Ramp Rise Rate Setup Program (page 4 9)
See
F Related parameters
All parameters in the program mode
Input type" Scaling upper limit" Scaling lower limit" Decimal point" (setup mode)
Step time/Rate of rise programming" (expansion mode)
5–12
Setting Range
1 to 16
to
to
Setting Range
SP lower limit to SP upper limit
Unit
Default
None
8
Unit
EU
Conditions of Use
Within the number of steps.
Default
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents