JPattern operation
F Repeating execu-
tion of the same
pattern
F Executing all
patterns
• To repeatedly execute the same pattern, set the number of times that the
pattern is to be executed in the pattern execution count" parameter
(program mode).
• The pattern execution count can be set up to 9999 (times). (Default is
0".)
• Patterns for which the pattern execution count" parameter is set to 0"
cannot be executed.
• The count of the currently executing pattern in the program can be veri
fied in the pattern execution count monitor" parameter (level 0 mode).
0" is indicated in this parameter when the controller of reset or in a
standby state.
• To execute all preset patterns in order from pattern 0, set the run all
enable" parameter (expansion mode) to
OFF".)
Pattern 0
• When a power interruption occurs during run all execution, if the op
eration at power ON" parameter (expansion mode) is set to
tinue", the currently executing pattern No. is held in memory. When
power is restored, program operation resumes from the pattern that was
being executed when the power was interrupted. (For details on opera
tion at power ON, see page 4 19.)
• Patterns whose pattern execution count" is set to 0" are skipped.
Pattern 0
"pattern execution count" of pattern 2 is set to 0
4.4 Program Operation
: ON". (Default
Pattern 1
Pattern 2
Pattern 1
Pattern 3
:
Time
: Con
Time
4–11