F Calibration:
0 to 10V
(8) Press the
key until the display changes to the data store display.
Press the
key. The No.2 display changes to [
conds later the calibration data is stored to internal memory. If you
press the [
] key when the No.2 display reads [
tion data is disabled.
(9) This completes calibration of the voltage input (0 to 5 V , 1 to 5 V).
Press the
key to return the display to [
This example describes how to calibrate a platinum resistance thermome
ter when the transfer output function is supported. If the transfer output
function is not supported, skips steps (4) to (7).
(1) When [
] is displayed, the 30 minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the ag
ing time when aging is required.
(2) Press the
key. The display changes to [
display). Set the STV output to 10 V . When the value on the No.2 dis
play has stabilized (changes of several digits max.), press the
to temporarily store the calibration data.
(3) Press the
key. The display changes to [
play). Set the STV output to 0 V . When the value on the No.2 display
has stabilized (changes of several digits max.), press the
temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (8). Press the
play changes to [
(5) Set the output to 20 mA by the
voltage on the digital multimeter. In the example on the left, the dis
play indicates that the value two digits smaller than before calibra
tion is 20 mA".
(6) Press the
key. The display changes to [
display).
(7) Set the output to 4 mA by the
voltage on the digital multimeter. In the example on the left, the dis
play indicates that the value two digits smaller than before calibra
tion is 4 mA".
(8) Press the
key until the display changes to the data store display.
Press the
key. The No.2 display changes to [
conds later the calibration data is stored to internal memory. If you
press the
key when the No.2 display reads [
data is disabled.
(9) This completes calibration of the voltage input (0 to 10 V). Press the
key to return the display to [
7.5 Calibrating Voltage Input
] (20 mA calibration display).
or
keys while monitoring the
or
keys while monitoring the
].
], and two se
], the calibra
].
] (10 V calibration
key
] (0 V calibration dis
key to
key. The dis
] (4 mA calibration
], and two se
], the calibration
7–11