SiENBE04-808_A
4.14 Discharge Pipe Temperature Control
F3
Remote Control
Display
Method of
An error is determined with the temperature detected by the discharge pipe thermistor.
Malfunction
Detection
If the temperature detected by the discharge pipe thermistor rises above
Malfunction
Decision
The error is cleared when the discharge pipe temperature has dropped below
Conditions
<20/25/35 class>
Stop temperatures
(1) above 45 Hz (rising), above 40 Hz (dropping)
(2) 30 ~ 45 Hz (rising), 25 ~ 40 Hz (dropping)
(3) below 30 Hz (rising), below 25 Hz (dropping)
<42 class>
Stop temperatures
(1) above 30Hz (rising), above 25Hz (dropping)
(2) below 30Hz (rising), below 25Hz (dropping)
<50 class>
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
Supposed
Causes
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Service Diagnosis
compressor stops.
(°C)
(°C)
110
95
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
(°C)
(°C)
110
97
105
92
99
86
(°C)
(°C)
110
95
108
93
Troubleshooting
°C, the
°C.
120