4.23 Output Overcurrent Detection
L5
Remote Control
Display
Method of
An output overcurrent is detected by checking the current that flows in the inverter DC section.
Malfunction
Detection
A position signal error occurs while the compressor is running.
Malfunction
A speed error occurs while the compressor is running.
Decision
An output overcurrent signal is fed from the output overcurrent detection circuit to the
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes (50 class: 5 minutes) without any
Poor installation condition
Supposed
Closed stop valve
Causes
Defective power module
Wrong internal wiring
Abnormal supply voltage
Defective outdoor unit PCB
Defective compressor
Service Diagnosis
microcomputer.
other error
Troubleshooting